Output Signal | 4/20 mA, 2-wire / V = 10.5-55 Vdc |
Differential Pressure Range | -14.5/0/145 PSI |
Smallest Calibration Span | 1.6 PSI |
Low Range Limit (LRL) | -72.5 PSI |
Upper Range Limit (URL) | 5801 PSI |
Static Pressure Limit | 5801 PSI |
High Side Overload Limit | 3626 PSI |
Low Side Overload Limit | 2321 PSI |
LCDDisplay | With LCD display (standard) |
Accuracy | 0.075% URL standard |
Stability | 0.2% per 5 years |
Temperature Range | - Working: -40/85°C (with display -20/70°C), -40/185°F (without display -4/158°F)
- Storage: -40/110°C (with display -40/85°C), -40/230°F (without display -40/185°F)
- Media: silicone oil filling: -40/120°C (-40/248°F)
|
Working Humidity | 5-100% at 40°C (104°F) |
Pressure Connection | 1/4” NPT (F) |
Housing | Rugged die-cast aluminum housing, painted blue |
Wetted Parts | 316L Stainless Steelwith PTFE o-ring (Hastelloy® C optional) |
Overload Pressure | Maximum of 3,600 or 6,000 psi |
Power Consumption | </- 500 mW at 24 VDC, 20.8 mA |
Vibration | - 20g, 20Hz…5kHz
- According to GB/T 1827.3 / IEC 61298-3 tests, <0.1% URL
|
Shock | 20g, 20Hz…5kHz |
Pressure Units | kPa, Mpa, bar, psi, mmHg, mmH2O, mH2O, inH2O, ftH2O, inHg, mHg, TORR, mbar, g/cm2, kg/cm2, Pa, ATM |
Temperature Units | Celsius, Fahrenheit |
Protection Class | EMI, ESD, RFI, reverse polarity protected |
Approvals | - CSA, for USA & Canada - Class I, Division 1, Group A,B,C and D T6 | Class II, Division 1 Group E, F and G T80oC | Class III
- Intertek, for USA & Canada - Class I, Zone 0 A Ex ia IIC T6 Gb | Class I, Division 1, Group A-D, T6 | – 40oC to 60oC
|
Protection Class | IP66 / IP67 |
Weight | 8.8 lbs (4.0 kg) |
Operational Life | 100 million cycles |