Mains |
Display size | 5 inches (diagonal) |
Backlight | Blue (On for 3 minute unless turned off manually) |
Mini-USB Port | For updating to latest version of firmware. |
Battery | 6 x AA (Battery life below based on alkaline type) |
Battery life | 350 hours (without backlight) |
Low battery indication | is displayed when the battery voltage drops below the operating level |
Auto Shut off | 30 minutes of inactivity when APO is activated |
Operating environment | 32 °F to 122 °F (0 °C to 50 °C) at <75%relative humidity |
Storage temperature | -4 °F to 140 °F (-20 °C to 60 °C), 0 to 80% RH(with battery removed) |
Temperature coefficient | 0.1 x (specified accuracy) per °C (0 °C to18 °C, 28 °C to 50 °C), per 0.6 °F (32 °F to 64 °F, 82 °F to 122 °F) |
Over range | "OL" or "-OL" is displayed |
Weight | 3.04 lbs (1.38 kg) |
Pressure |
Connector Type | Standard 1/4 NPT male flare fitting |
Range | 29" HgV to 580 Psig (English), 74 cmHgV to 0 to 4000KPa(Metric) |
Resolution | 0.1 psi/inHg; 1 kPa/cmHg |
Accuracy | 29" HgV to 0" HgV ±0.2" HgV74 cmHgV to 0 cmHgV ±1 cmHgV0 to 200 Psig ±1 Psi; 0 to 1378 KPa ±7 KPa; 0 to 1.378MPa±0.007MPa; 0 to 13.78 bar ±0.07 bar200 to 580 Psig ±0.3%+1 Psi; 1378 to 4000KPa ±0.3%+7 Kpa;1.378 to 4.000MPa ±0.3%+0.007MPa; 13.78 to 40.00bar±0.3%+0.07bar |
Maximum overload pressure | 800 psig |
Units | Psig, kPa, MPa, bar, inHg, and cmHg |
Microns for Vacuum |
Connector Type | Standard 1/4" NPT male flare fitting |
Range | 0 to 9999 microns of mercury |
Resolution | 1 micron (0 to 2000 microns), 250 microns (2001 to5000 microns), 500 microns (5001 to 8000 microns), 1000 microns(8001 to 9999 microns) |
Accuracy | ±(5% of reading + 5 microns), 50 to 1000 microns |
Maximum Overload pressure | 580 psig |
Units | Microns of mercury |
Temperature |
Sensor type | K-Type thermocouple |
Range | -95 °F to 999.9 °F (-70 °C to 537.0 °C) |
Resolution | 0.1 °F/ °C |
Accuracy | ±(1.0 °F) -95 °F to 199.9 °F; ±(0.5 °C) -70 °C to 93 °C±(2.0 °F) 200 °F to 999.9 °F; ±(1.0 °C) 93 °C to 537.0 °C Note All accuracies are after a field calibration. |
Refrigerants |
The P-T charts of the following 45 refrigerants come preprogrammed into your SMAN. In your SMAN the refrigerants are listed in order of most commonly used. Here, they are listed in numerical order. R11, R113, R114, R12, R123, R1234YF, R124, R125, R13, R134A, R22, R23, R32, R401A(MP39), R401B, R402A, R402B, R404A, R406A, R407A, R407C, R407F, R408A, R409A, R410A, R414B (Hotshot), R416A, R417A, R417C (HOT SHOT 2), R420A, R421A, R421B, R422A, R422B(NU22B), R422C(Oneshot), R422D, R424A, R427A, R434A(RS-45), R438A(MO99), R500, R502, R503, R507A, R508B (Suva95) |